S323: IP65 Differential Pressure Transmitter |
|
|
 |
Model |
: S323 |
 |
Range |
: -500 to 500 mmwc |
 |
Output |
: 0-10 V / 4-20 mA |
 |
Accuracy |
: ±0.25% of F.S |
 |
Media |
: Air / Gases |
 |
Display |
: None |
|
|
Specifications |
|
 |
Maximum Pressure |
: Ranges ≤ 5 PSI (35 kPa) = 15 PSI
(100 kPa) Max |
 |
Storage |
: Ranges > 5 PSI (35 kPa) = 30 PSI
(200 kPa) Max |
 |
Media compatibility |
: Air and compatible non combustible,
non corrosive gasses |
 |
Accuracy |
: Ranges ≤ 4” w.c. (1 kPa) 1.0%
Ranges ≥ 5” w.c. (1.25 kPa) 0.25% |
Temperature Ranges |
 |
Compensated |
: 15° to 120°F (-10° to 50°C) |
 |
Operating |
: -10° to 155°F (-25° to 70°C) |
 |
Thermal Effect |
: +/- 0.028% FS/°F (+/- 0.050%/° C) |
 |
Stability |
: +/- 0.25% FS/year |
 |
Output Signal |
: 4-20 mA, 2 wire or 0-10V |
 |
Loop Resistance |
: 250 Ω @ 24 VDC |
 |
Power Supply |
: 12-30 VDC |
 |
Enclosure Rating |
: IP 65 |
 |
Electrical Connections |
: screw terminals |
 |
Electrical Entry |
: PG7 cable gland |
 |
Process Connection |
: Barbed fittings for 3/16” flexible
tubing |
 |
Agency Approvals |
: CE |
|
|
|
|
|
|
|